3000 kVA Substation Transformer

Price range: $60,250.00 through $158,500.00

Substation Transformer, 15kV, 25kV, 35kV, 46kV, 69kV primary, 4160V, 480V, 12470V, 24940V, 34500V secondary. Aluminum windings, mineral oil, ONAN cooled, built to ANSI/IEEE C57.12. 58 voltage configurations available.

Lead time: 12–16 weeks. Copper windings and natural ester fluid available on request.

- +
Contact Us
SKU: BPS-SUB-3000K Category:
  • UL Listed options available
  • B.A.B.A.-compliant options available
  • Factory test report with every unit
Ordering online? Stock moves fast, so call 601-912-3512 or email sales@bearpowersolutions.com to confirm availability before you check out. If a unit has sold, we’ll quote a build slot and confirm the lead time in writing.

The 3000 kVA substation transformer is built for primary distribution service, stepping medium- or high-voltage supply down to a distribution or utilization voltage. It is supplied with throat or bus connections for integration into a switchgear lineup. At 3000 kVA radiator cooling becomes standard and the unit is typically the primary supply for a plant or campus.

Specifications

Rating 3000 kVA
Phase Three phase
Primary voltage class 15kV / 25kV / 35kV / 46kV / 69kV
Secondary voltage class 4160V / 480V / 12470V / 24940V / 34500V
Basic insulation level (BIL) 95 kV / 125 kV / 150 kV / 250 kV / 350 kV
Frequency 60 Hz
Temperature rise 65 °C
Winding material Aluminum
Insulating fluid Mineral oil, Type I
Cooling class ONAN
Taps Plus/minus 2 x 2.5% full-capacity below and above nominal
Enclosure ANSI 70 gray
Feed configuration Per application
Standards ANSI/IEEE C57.12, NEMA
Lead time 12–16 weeks

Full-load current

Rated secondary current for a 3000 kVA unit at each available secondary voltage. Use these figures for conductor, breaker and bus sizing.

Secondary voltage Full-load current
4160Y/2400 416 A
480Y/277 3,608 A
12470Y/7200 139 A
13200Y/7620 131 A
13800 Delta 126 A
24940Y/14400 69 A
34500Y/19920 50 A

Rated primary current at each available primary voltage:

Primary voltage Full-load current
2400 Delta 722 A
4160 Delta 416 A
4160Y/2400 416 A
4800 Delta 361 A
7200 Delta 241 A
12000 Delta 144 A
12470Y/7200 139 A
13200 Delta 131 A
13200Y/7620 131 A
13800 Delta 126 A
13800Y/7970 126 A
22900Y/13200 76 A
24940Y/14400 69 A
34500 Delta 50 A
34500Y/19920 50 A
46000 Delta 38 A
69000 Delta 25 A

Typical applications

  • Solar and wind collection substations
  • Plant primary substations
  • Large campus distribution
  • Utility distribution substations

Construction

Standard construction is aluminum windings in a sealed tank with mineral oil, ONAN cooled, 65 °C rise. The tank is welded and finished in ANSI 70 gray. A five-position no-load tap changer provides plus and minus two 2.5% full-capacity taps. Copper windings and natural ester fluid are available on request.

Standards and compliance

  • Built to ANSI/IEEE C57.12 and applicable NEMA standards
  • Factory test report supplied with every unit
  • Supplied and supported by Bear Power Solutions, Jackson, Mississippi

Frequently asked questions

What voltages is the 3000 kVA available in?

The 3000 kVA is available with 15kV / 25kV / 35kV / 46kV / 69kV primary and 4160V / 480V / 12470V / 24940V / 34500V secondary. That is 58 configurations in total. Every voltage inside a class carries the same price and the same basic insulation level.

What is the lead time on a 3000 kVA?

Lead times are 12–16 weeks from order confirmation, depending on configuration and current factory loading. Non-standard voltages, accessories, custom enclosure work and non-standard fluid or winding material extend that. Confirm the delivery date with Bear Power Solutions before committing to a project schedule.

Can this be supplied with a switchgear throat connection?

Yes. Substation transformers are commonly supplied with primary and secondary throat or bus connections for direct integration into a switchgear lineup. Specify the mating arrangement at time of quotation.

Can the 3000 kVA be supplied with copper windings or natural ester fluid?

Standard catalog construction is aluminum windings with mineral oil. Copper windings and natural ester fluid are available on request. Both affect price and lead time, so request a quotation for a non-standard build.

What standards does the 3000 kVA meet?

Units are built to ANSI/IEEE C57.12 and applicable NEMA standards. Factory test reports are provided with every unit.

Sizing the 3000 kVA

At its lowest available secondary voltage the 3000 kVA draws 3,608 A at full load; at its highest it draws 50 A. That spread is what makes secondary voltage selection an installation-cost decision as much as an electrical one – the higher voltage cuts conductor size for the same delivered power.

Secondary current at this rating is high enough that parallel conductor runs or busway are normally required on the low-voltage side. Confirm the secondary termination arrangement and available bus space before ordering.

Request a quote

For a firm price on a 3000 kVA in a specific voltage configuration, or for a non-standard build with copper windings, natural ester fluid or custom accessories, send the details below and Bear Power Solutions will respond with a written quotation.

Weeks: 0
How quick do you need this Transformer(s)?
Primary Voltage

12000 Delta, 12470Y/7200, 13200 Delta, 13200Y/7620, 13800 Delta, 13800Y/7970, 22900Y/13200, 2400 Delta, 24940Y/14400, 34500 Delta, 34500Y/19920, 4160 Delta, 4160Y/2400, 46000 Delta, 4800 Delta, 69000 Delta, 7200 Delta

Secondary Voltage

12470Y/7200, 13200Y/7620, 13800 Delta, 24940Y/14400, 34500Y/19920, 4160Y/2400, 480Y/277

// Request a quote

Firm price.
Written quote.

Tell us the kVA, primary and secondary voltage, quantity and where it’s going. We’ll come back with price, lead time and freight in writing. Copper windings, natural ester fluid and custom accessories are quoted to spec.

Facilities
About 25,000 sq ft across two locations
Lynch Street
5570 John R Lynch St., Jackson, MS · 17,000+ sq ft for distribution, assembly and transformer oil
Compliance
UL Listed options available · B.A.B.A.-compliant options available
// Trusted by
  • Supermicro logo
  • Flex logo
  • Memphis Light, Gas and Water (MLGW) logo
  • City of Fort Collins logo
  • City Utilities logo
  • Athens Utilities Board logo
  • TCEC logo
  • ALLETE Clean Energy logo
  • Entegrity logo
  • ASRC Federal logo
  • Lockheed Martin logo
  • DAVIS-MONTHANAir Force Base
  • FAIRCHILDAir Force Base
  • Oklahoma City University logo
  • Chicago Housing Authority logo
Shopping Cart