5000 kVA Three-Phase Pad-Mount Transformer

Price range: $113,850.00 through $136,400.00

Three-Phase Pad-Mount Transformer, 15kV, 25kV, 35kV primary, 600V secondary. Aluminum windings, mineral oil, ONAN cooled, built to ANSI/IEEE C57.12 and DOE 2016 efficiency. 11 voltage configurations available.

Lead time: As little as 10 weeks. Copper windings and natural ester fluid available on request.

Contact Us
SKU: BPS-3PH-PAD-5000K Category:

The 5000 kVA three-phase pad-mount transformer is a compartmental, dead-front distribution unit for commercial and industrial service. High- and low-voltage compartments sit side by side behind lockable steel doors, with underground cable entry through the base. At 5000 kVA this is unit-substation class equipment rather than a conventional pad-mount. It is specified for heavy industry, large data center campuses and utility distribution.

Specifications

Rating 5000 kVA
Phase Three phase
Primary voltage class 15kV / 25kV / 35kV
Secondary voltage class 600V
Basic insulation level (BIL) 95 kV / 125 kV / 150 kV
Frequency 60 Hz
Temperature rise 65 °C
Winding material Aluminum
Insulating fluid Mineral oil, Type I
Cooling class ONAN
Taps Plus/minus 2 x 2.5% full-capacity below and above nominal
Enclosure Munsell Green 7GY3.29/1.5, tamper-resistant
Feed configuration Radial feed, dead front
Standards ANSI/IEEE C57.12, NEMA, DOE 2016 efficiency
Lead time As little as 10 weeks

Full-load current

Rated secondary current for a 5000 kVA unit at each available secondary voltage. Use these figures for conductor, breaker and bus sizing.

Secondary voltage Full-load current
600Y/347 4,811 A

Rated primary current at each available primary voltage:

Primary voltage Full-load current
7200 Delta 401 A
12000 Delta 241 A
12470Y/7200 231 A
13200 Delta 219 A
13200Y/7620 219 A
13800 Delta 209 A
13800Y/7970 209 A
22900Y/13200 126 A
24940Y/14400 116 A
34500 Delta 84 A
34500Y/19920 84 A

Typical applications

  • Large data center campuses
  • Utility distribution substations
  • Mining and aggregate operations
  • Heavy industrial process loads

Construction

Standard construction is aluminum windings in a sealed tank with mineral oil, ONAN cooled, 65 °C rise. The tank is welded and finished in Munsell Green 7GY3.29/1.5. A four-position no-load tap changer provides plus and minus two 2.5% full-capacity taps. Copper windings and natural ester fluid are available on request.

Standards and compliance

  • Built to ANSI/IEEE C57.12 and applicable NEMA standards
  • Meets DOE 2016 efficiency requirements
  • Factory test report supplied with every unit
  • Manufactured and supported by Bear Power Solutions, Brandon, Mississippi

Frequently asked questions

What voltages is the 5000 kVA available in?

The 5000 kVA is available with 15kV / 25kV / 35kV primary and 600V secondary. That is 11 configurations in total. Every voltage inside a class carries the same price and the same basic insulation level.

What is the lead time on a 5000 kVA?

Lead times start at 10 weeks from order confirmation, depending on configuration and current factory loading. Non-standard voltages, accessories, custom enclosure work and non-standard fluid or winding material extend that. Confirm the delivery date with Bear Power Solutions before committing to a project schedule.

Is this a dead-front or live-front transformer?

Standard construction is dead-front with loadbreak elbow connections on the primary. Live-front construction is available on request and should be specified at the time of quotation.

Can the 5000 kVA be supplied with copper windings or natural ester fluid?

Standard catalog construction is aluminum windings with mineral oil. Copper windings and natural ester fluid are available on request. Both affect price and lead time, so request a quotation for a non-standard build.

What standards does the 5000 kVA meet?

Units are built to ANSI/IEEE C57.12 and applicable NEMA standards, and meet DOE 2016 efficiency requirements. Factory test reports are provided with every unit.

Sizing the 5000 kVA

At its lowest available secondary voltage the 5000 kVA draws 4,811 A at full load; at its highest it draws 4,811 A. That spread is what makes secondary voltage selection an installation-cost decision as much as an electrical one – the higher voltage cuts conductor size for the same delivered power.

Secondary current at this rating is high enough that parallel conductor runs or busway are normally required on the low-voltage side. Confirm the secondary termination arrangement and available bus space before ordering.

Request a quote

For a firm price on a 5000 kVA in a specific voltage configuration, or for a non-standard build with copper windings, natural ester fluid or custom accessories, send the details below and Bear Power Solutions will respond with a written quotation.

Weeks: 0
How quick do you need this Transformer(s)?
Primary Voltage

12000 Delta, 12470Y/7200, 13200 Delta, 13200Y/7620, 13800 Delta, 13800Y/7970, 22900Y/13200, 24940Y/14400, 34500 Delta, 34500Y/19920, 7200 Delta

Secondary Voltage

600Y/347

Shopping Cart

PLEASE CALL 601-912-3512 OR EMAIL SALES@BEARPOWERSOLUTIONS.COM TO VERIFY STOCK BEFORE SUBMITTING AN ORDER ON OIL FILLED TRANSFORMERS