1000 kVA Three-Phase Pad-Mount Transformer

Price range: $35,128.50 through $64,955.00

Three-Phase Pad-Mount Transformer, 15kV, 25kV, 35kV primary, 240V, 600V secondary. Aluminum windings, mineral oil, ONAN cooled, built to ANSI/IEEE C57.12 and DOE 2016 efficiency. 105 voltage configurations available.

Lead time: As little as 10 weeks. Copper windings and natural ester fluid available on request.

Contact Us
SKU: BPS-3PH-PAD-1000K Category:

The 1000 kVA three-phase pad-mount transformer is a compartmental, dead-front distribution unit for commercial and industrial service. High- and low-voltage compartments sit side by side behind lockable steel doors, with underground cable entry through the base. At 1000 kVA it covers mid-size commercial buildings, manufacturing plants, apartment complexes and data center support loads.

Specifications

Rating 1000 kVA
Phase Three phase
Primary voltage class 15kV / 25kV / 35kV
Secondary voltage class 240V / 600V
Basic insulation level (BIL) 95 kV / 125 kV / 150 kV
Frequency 60 Hz
Temperature rise 65 °C
Winding material Aluminum
Insulating fluid Mineral oil, Type I
Cooling class ONAN
Taps Plus/minus 2 x 2.5% full-capacity below and above nominal
Enclosure Munsell Green 7GY3.29/1.5, tamper-resistant
Feed configuration Radial feed, dead front
Standards ANSI/IEEE C57.12, NEMA, DOE 2016 efficiency
Lead time As little as 10 weeks

Full-load current

Rated secondary current for a 1000 kVA unit at each available secondary voltage. Use these figures for conductor, breaker and bus sizing.

Secondary voltage Full-load current
208Y/120 2,776 A
240 Delta 2,406 A
240/120 Delta 2,406 A
415Y/240 1,391 A
480 Delta 1,203 A
480Y/277 1,203 A
600Y/347 962 A

Rated primary current at each available primary voltage:

Primary voltage Full-load current
2400 Delta 241 A
4160 Delta 139 A
4160Y/2400 139 A
4800 Delta 120 A
7200 Delta 80 A
12000 Delta 48 A
12470Y/7200 46 A
13200 Delta 44 A
13200Y/7620 44 A
13800 Delta 42 A
13800Y/7970 42 A
22900Y/13200 25 A
24940Y/14400 23 A
34500 Delta 17 A
34500Y/19920 17 A

Typical applications

  • Apartment and mixed-use developments
  • Data center mechanical and support loads
  • Cold storage and food processing
  • Mid-size commercial buildings
  • Manufacturing plants

Construction

Standard construction is aluminum windings in a sealed tank with mineral oil, ONAN cooled, 65 °C rise. The tank is welded and finished in Munsell Green 7GY3.29/1.5. A four-position no-load tap changer provides plus and minus two 2.5% full-capacity taps. Copper windings and natural ester fluid are available on request.

Standards and compliance

  • Built to ANSI/IEEE C57.12 and applicable NEMA standards
  • Meets DOE 2016 efficiency requirements
  • Factory test report supplied with every unit
  • Manufactured and supported by Bear Power Solutions, Brandon, Mississippi

Frequently asked questions

What voltages is the 1000 kVA available in?

The 1000 kVA is available with 15kV / 25kV / 35kV primary and 240V / 600V secondary. That is 105 configurations in total. Every voltage inside a class carries the same price and the same basic insulation level.

What is the lead time on a 1000 kVA?

Lead times start at 10 weeks from order confirmation, depending on configuration and current factory loading. Non-standard voltages, accessories, custom enclosure work and non-standard fluid or winding material extend that. Confirm the delivery date with Bear Power Solutions before committing to a project schedule.

Is this a dead-front or live-front transformer?

Standard construction is dead-front with loadbreak elbow connections on the primary. Live-front construction is available on request and should be specified at the time of quotation.

Can the 1000 kVA be supplied with copper windings or natural ester fluid?

Standard catalog construction is aluminum windings with mineral oil. Copper windings and natural ester fluid are available on request. Both affect price and lead time, so request a quotation for a non-standard build.

What standards does the 1000 kVA meet?

Units are built to ANSI/IEEE C57.12 and applicable NEMA standards, and meet DOE 2016 efficiency requirements. Factory test reports are provided with every unit.

Sizing the 1000 kVA

At its lowest available secondary voltage the 1000 kVA draws 2,776 A at full load; at its highest it draws 962 A. That spread is what makes secondary voltage selection an installation-cost decision as much as an electrical one – the higher voltage cuts conductor size for the same delivered power.

Secondary current at this rating is high enough that parallel conductor runs or busway are normally required on the low-voltage side. Confirm the secondary termination arrangement and available bus space before ordering.

Request a quote

For a firm price on a 1000 kVA in a specific voltage configuration, or for a non-standard build with copper windings, natural ester fluid or custom accessories, send the details below and Bear Power Solutions will respond with a written quotation.

Weeks: 0
How quick do you need this Transformer(s)?
Primary Voltage

12000 Delta, 12470Y/7200, 13200 Delta, 13200Y/7620, 13800 Delta, 13800Y/7970, 22900Y/13200, 2400 Delta, 24940Y/14400, 34500 Delta, 34500Y/19920, 4160 Delta, 4160Y/2400, 4800 Delta, 7200 Delta

Secondary Voltage

208Y/120, 240 Delta, 240/120 Delta, 415Y/240, 480 Delta, 480Y/277, 600Y/347

Shopping Cart

PLEASE CALL 601-912-3512 OR EMAIL SALES@BEARPOWERSOLUTIONS.COM TO VERIFY STOCK BEFORE SUBMITTING AN ORDER ON OIL FILLED TRANSFORMERS